Column Load Calculator
Calculate axial load on columns including self-weight, slab load, beam load, wall load, and tributary area — for RCC column design to ACI 318, BS 8110 and IS 456.
RCC Column Load Calculator
Axial Load · Self Weight · Tributary Area Method
Column Load Results
CalculatedHow Column Load Calculation Works
Column loads are calculated using the Tributary Area Method — each column carries the loads from the floor area it supports. This is the standard method used in Pakistani residential and commercial building design.
Step-by-Step Method
Typical Column Sizes for Pakistan Residential Buildings
| Floors | Tributary Area | Approx Load | Min Column Size | Concrete |
|---|---|---|---|---|
| G+0 (1 floor) | 12–16 m² | 100–200 kN | 230×230 mm | M20 |
| G+1 (2 floors) | 12–16 m² | 200–400 kN | 230×300 mm | M20 |
| G+2 (3 floors) | 12–20 m² | 400–700 kN | 300×300 mm | M25 |
| G+3 (4 floors) | 12–20 m² | 700–1200 kN | 350×350 mm | M25 |
| G+4 (5 floors) | 15–25 m² | 1200–2000 kN | 400×400 mm | M30 |
| G+5+ (6+ floors) | 15–25 m² | 2000+ kN | 450×450+ mm | M30+ |
Sizes are indicative only. Actual design depends on loading, eccentricity, and reinforcement details.
🧾 Worked Example: Interior Column of a G+2 House
Consider an interior ground floor column, 300 × 300 mm, carrying three floors with a storey height of 3.0 m. The column grid gives it a tributary width of 4.5 m one way and 4.0 m the other. We use the calculator defaults for loads: slab dead load 5 kN/m², live load 3 kN/m², beams 5 kN/m, walls 12 kN/m, M25 concrete and a load factor of 1.5.
| Step | Working | Result |
|---|---|---|
| Tributary area | 4.5 × 4.0 | 18.0 m² |
| Slab load per floor | (5 + 3) × 18 | 144.0 kN |
| Beams per floor | 5 × (4.5 + 4.0) | 42.5 kN |
| Walls per floor | 12 × (4.5 + 4.0) | 102.0 kN |
| Load per floor | 144 + 42.5 + 102 | 288.5 kN |
| Column self weight | 0.3 × 0.3 × 3 × 25 × 3 | 20.3 kN |
| Total service load P | 288.5 × 3 + 20.3 | 885.8 kN |
| Factored load Pu | 885.8 × 1.5 | 1,328.6 kN |
| Area by concrete alone | 1,328,600 / (0.4 × 25) | 132,860 mm² |
The 300 × 300 column gives only 90,000 mm², so plain concrete alone is not enough. That does not mean the size fails. The calculator's area figure ignores the steel, which carries a real share of the load. With IS 456 the short column capacity is 0.4 fck Ac + 0.67 fy Asc. Using 4 bars of 20 mm plus 4 bars of 16 mm (2,061 mm², about 2.3%) in Fe 415 steel:
So the column works on paper, but with little margin and fairly heavy steel. Many designers would go to 300 × 375 or 350 × 350 at the ground floor here and reduce the size or the steel on the upper floors.
How the load builds up with floors
| Floors carried | Factored load Pu | Area by concrete alone |
|---|---|---|
| 1 | 443 kN | 44,290 mm² (about 210 × 210) |
| 2 | 886 kN | 88,580 mm² (about 300 × 300) |
| 3 | 1,329 kN | 132,860 mm² (about 365 × 365) |
| 4 | 1,772 kN | 177,150 mm² (about 420 × 420) |
| 6 | 2,657 kN | 265,730 mm² (about 515 × 515) |
Same grid and loads as above, M25, factor 1.5, a 300 × 300 self weight per floor. Steel lets you go smaller than these sizes, which is why the reference table shows lighter sections.
Practical Checks and Common Mistakes
- Edge and corner columns. An edge column on the same grid might carry 4.5 × 2.0 m of slab and get about 852 kN factored for three floors. The load is lower, but the slab and beams pull on one side only, so it also takes a bending moment. Do not size it on axial load alone.
- Counting walls twice or not at all. Enter the wall load only for walls that actually sit on the beams framing into this column. Full height external walls on every floor are a large part of the total.
- Live load reduction. IS 875 Part 2 allows a reduction in imposed load for columns carrying several floors (10% for two floors, 20% for three, up to 50% for many). The calculator does not apply it, so its result is on the safe side.
- Slender columns. The simple formula holds for short columns. When the effective height is more than about 12 times the smaller side, extra moments from buckling must be added. A 230 mm column 3.5 m tall is already close to this limit.
- Minimum size. Many codes and seismic provisions call for at least 300 mm on the smaller side for frame columns. Thin 230 mm columns are common in small houses, but they leave very little room for bars and concrete to flow.
- Foundation load. Use the service load P, not Pu, when you check soil bearing pressure for the footing.
